` Celair Profile Series Fresh Air Conditioning Installation Instructions Profile 500, 600, 750, 850
Installation Instructions 3.0 Unit Installation Profile 3.3.8. Lift the fan deck onto the roof and reinstall into the unit. Ensure the venturi is
Installation Instructions 3.0 Unit Installation Profile The last bend to each ceiling register must be a smooth rad
Installation Instructions 4.0 Connections Profile 4. CONNECTIONS All water connections must be carried out by a licensed plumber. A plumbing certi
Installation Instructions 4.0 Connections Profile • Unit water connection a ½” BSP female flexible connection. Use the flexible connector supplied
Installation Instructions 4.0 Connections Profile 4.3.2. Fitting the Enviroflow Water Conservation System - Optional Accessory The Enviroflow wat
Installation Instructions 4.0 Connections Profile OPTION 1. A discharge point to a roof gutter pop outlet, providing the downpipe is not used for t
Installation Instructions 4.0 Connections Profile OPTION 4. A sanitary drainage system via a tundish in one of the following forms in accordance wi
Installation Instructions 4.0 Connections Profile OPTION 5. An absorption pit. Provided the following conditions can be met: • Only permitted wh
Installation Instructions 4.0 Connections Profile 4.4. Electrical 4.4.1. Wiring – Important Notes • A LICENSED ELECTRICIAN must carry out 240-vol
Installation Instructions 4.0 Connections Profile • Drill a 50mm (2”) hole in the dropper to bring the service lead and controller cable into the
Installation Instructions Table of Contents Profile 1. INTRODUCTION____________________________________________________ 3 1.1. Important Notes ____
Installation Instructions 5.0 Commissioning Profile 5. COMMISSIONING 5.1. Water Levels 5.1.1. Turn water on to unit and allow unit to fil
Installation Instructions 5.0 Commissioning Profile • With normal town water supply, bleed rate should be adjusted so that the discharge is not le
Installation Instructions 5.0 Commissioning Profile 5.7. Commissioning Check List You must complete, date and sign the ‘tick box’ checklist in the
Installation Instructions 5.0 Commissioning Profile Ductwork and general The Enviroseal functions correctly with the shutters opening downwards
6052271/A Manufactured by Manufactured by Climate Technologies Climate Technologies ABN 13 001 418 042 ABN 13 001 418 042 26 Nylex Avenue 2
Installation Instructions 1.0 Introduction Profile 1. INTRODUCTION Please take the time to fully read this Installation manual. Failure to follow
Installation Instructions 1.0 Introduction Profile 1.2.3. Safety and O.H.&S. Requirements • It is the responsibility of the dealer / installer
Installation Instructions 2.0 Unit Location Profile 2. UNIT LOCATION 2.1 Unit Location Check List • EPA - A correct installed unit will perform t
Installation Instructions 3.0 Unit Installation Profile 3. UNIT INSTALLATION 3.1. Installing the Dropper Duct All Celair Fresh Air Conditioners are
Installation Instructions 3.0 Unit Installation Profile 3.2. Installing the Enviroseal Duct Shutter - Optional Accessory Ste
Installation Instructions 3.0 Unit Installation Profile 3.3. Installing the Air Conditioner 3.3.1. Remove 4 Louvre panels from unit and place in a
Installation Instructions 3.0 Unit Installation Profile NOTE: Handle the fan/venturi assembly with care, as the fan blade is not protected by the